Estimating the OD
- Determine the gauge and type of wire.
- By using CHART – A, determine the O.D. of the wire.
- Determine the number of conductors to be used in the MB Cable.
- By using CHART – B, determine the O.D. Factor.
- Multiply the O.D. of the wire by the O.D. Factor to estimate the O.D. of the MB Cable
Choose THHN stranded wire :
Choose Number of Conductors :
MB Cable OD :
Choose THHN Solid wire :
Choose XHHW2 stranded wire :
Common Wire ODs and Weights – Chart A
THHN | Stranded | Solid |
---|---|---|
18 | .088/9 | .083/8 |
16 | .093/13 | .094/12 |
14 | .112/18 | .104/17 |
12 | .131/27 | .121/25 |
10 | .164/41 | .152/39 |
8 | .216/71 | |
6 | .253/99 | |
4 | .322/168 | |
3 | .350/204 | |
2 | .381/254 | |
1 | .483/319 |
XHHW – 2 | Stranded |
---|---|
14 | .133/18 |
12 | .152/26 |
10 | .175/39 |
Chart B
Number of Wires | Column OD Factor |
---|---|
3 | 2.15 |
5 | 2.8 |
7 | 3. |
9 | 3.58 |
12 | 4.15 |
16 | 4.8 |
19 | 5. |
24 | 5.5 |
28 | 6. |
33 | 6.5 |
37 | 7. |
43 | 7.5 |
49 | 8. |
55 | 8.5 |
61 | 9. |
69 | 9.5 |
76 | 10. |
84 | 10.5 |
91 | 11. |
100 | 11.5 |
109 | 12. |
118 | 12.5 |
127 | 13. |
135 | 13.5 |
148 | 14 |
159 | 14.5 |
169 | 15. |
181 | 15.5 |
193 | 16. |
205 | 16.5 |
217 | 17. |
231 | 17.5 |
244 | 18. |
257 | 18.5 |
271 | 19 |
286 | 19.5 |
301 | 20. |
316 | 20.5 |
331 | 21. |
348 | 21.5 |
364 | 22. |
381 | 22.5 |
397 | 23. |
415 | 23.5 |
433 | 24. |